Medium Voltage Products
Overhead Line Insulation Sleeve
AOPS

Technical Data
Properties | Test Methods | Typical Values |
Tensile strength (MPa) | GB/T 1040-92 | ≥ 10 |
Elongation at break (%) | GB/T 1040-92 | ≥ 500 |
Dielectric strength (kV/mm) | GB/T 1408-89 | ≥ 20 |
Volume resistance (Ω.cm) | GB/T 1410-2006 | ≥ 1 x 1013 |
Dielectric constant | GB/T 1409-2006 | ≤ 3.0 |
Flammability (Oi) | GB/T 2406-1993 | ≥ 27 |
Microtherm flexility (-40°C, 4hrs) | ASTM D 2671 | No Cracking |
Water absorption (%) | GB/T 1034-98 | ≤ 0.5 |
Description
AOPS has been designed to provide reliable insulation and protection on bare overhead line systems preventing electrical outages caused by accidental contact from trees, animals and other objects. Outages may also occur in windy conditions between power lines and when these lines are close to steel structures.
Features
- Suitable for voltage up to 35kV
- Prevent tapping by hooking and other means
- Excellent UV and abrasion resistance properties resulting in outstanding resistance to weathering (harsh environments)
- Erosion and tracking resistant
- Quick and easy installation
- Installation on live installation by means of specially designed tools
- Red mastic sealant available for improved performance
- Colours – red / yellow / green / black

AOPST1 – Application Tool
Dimensions

Product | Sleeve Size (∅) |
Voltage Rating (kV) |
Conductor Size (mm²) | Max Conductor OD (mm) | Standard Length (m) |
AOPS14/35 | 14 | 1 – 35 | ≤ 70 | 12 | 20 |
AOPS18/35 | 18 | 1 – 35 | 95 | 18 | 20 |
AOPS20/35 | 20 | 1 – 35 | 120-150 | 22 | 20 |
AOPS28/35 | 28 | 1 – 35 | 185-240 | 30 |
20 |
AOPS38/35 | 38 | 1 – 35 | ≥ 300 | 38 |
20 |
74 Technology Crescent, Klipriver Business Park, Klipriver
Tel: 011 868 3783 Fax: 011 868 3773
E-mail: office@airshrinksa.co.za Website: www.cip-airshrink.co.za